ꢀ MQP240
Diesel Generator
Prime rating — 240 kW (300 kVA)
standby rating — 260 kW (330 kVA)
3-Phase, 60 Hertz, 0.8 PF
standard Features
Heavy duty, turbocharged, direct injection diesel engine
provides maximum reliability.
Complete engine analog instrumentation includes DC
ammeter, oil pressure gauge, fuel gauge, water temp. gauge,
tachometer/hour meter, preheat indicator, manual engine
speed control, emergency shutdown monitors, and emergency
stop button.
Brushless alternator reduces service and maintenance
requirements and meets temperature rise standards for Class
F insulation systems.
Complete generator analog instrumentation includes
voltage regulator control, ammeter phase selector switch,
voltmeter phase selector switch, AC voltmeter, AC ammeter,
frequency meter, panel light, and circuit breaker.
open delta alternator design provides virtually unlimited
excitation for maximum motor starting capability.
automatic voltage regulator (avr) provides precise
regulation.
automatic safety shutdown system monitors the water
temperature, engine oil pressure, overspeed, and overcrank.
Warning lights indicate abnormal conditions.
electronic governor system with idle switch maintains
frequency to 0.25%.
autostart/stop controlallows generator to start automatically
in the event of a commercial power failure.
Full load acceptance of standby nameplate rating in one
step (NFPA 110, para 5-13.2.6).
Complete power panel. Fully covered;three-phase terminals
and single phase receptacles allow fast and convenient
hookup for most applications including temporary power
boxes, tools and lighting equipment. All are NEMA standard.
sound attenuated, weather resistant, steel housing
provides operation at 73 dB(A) at 23 feet. Fully lockable
enclosure allows safe unattended operation.
Fuel/water separator removes condensation from fuel for
extended engine life.
two stage air filter
simultaneous single and three phase power
emergency stop switch
e-Coat primer with polyurethane enamel finish coat.
low coolant level shutdown system provides protection
from critically low coolant levels. Includes control panel
warning light.
Battery switch
documentation box
ePa emissions certified - Tier 3 emissions compliant.
MQP240 — diesel generator — rev. #0 (10/05/12)
ꢀ MQP240
Diesel Generator
oPtional generator Features
MQ POWER DECIBEL LEVELS
U
Our soundproof housing
allows substantially
lower operating noise
levels than competitive
designs. WhisperWatts
are at home on
Battery charger — provides fully automatic and self-
adjusting charging to the generator's battery system.
Subway / truck traffic
90
80
70
Jacket water heater — for easy starting in cold weather
climates.
Average city traffic
MQP240 at 23 feet
Inside car at 60 mph
special batteries — long life batteries provide extra engine
cranking power.
construction sites, in
residential
Air conditioner at 20 feet
Normal conversation
60
50
neighborhoods, and at
hospitals — just about
anywhere.
spring isolaters — provides extra vibration protection for
standby applications.
trailer mounted package — highway legal trailer with
electric or surge brakes with triple axle configuration. Extra
capacity fuel tanks are also available.
DECIBELS
oPtional Control Features
audible alarm — alerts operator of abnormal conditions.
generator outPut Panel
oPtional Fuel Cell Features
trailer fuel tank — fuel cell located in the trailer.
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES
subbase fuel cell (double wall) — contains a leak
sensor, low fuel level switch, and a secondary containment
tank. UL142 listed.
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
12 hours of minimum run time.
24 hours of minimum run time.
oPtional outPut ConneCtions
GFCI RECEPTACLES (2)
120V, 20 AMP
CS-6369 TWIST-LOCK
RECEPTACLES (3)
240Y/139, 50 AMPS
Cam-loks — provides quick disconnect alternative to bolt-
on connectors.
Pin and sleeve Connectors — provides industry standard
connectors for all voltage requirements.
U
V
W
O
output Cable — available in any custom length and size
configuration.
1Ø AND 3Ø
120-480 VAC OUTPUT
LUG TERMINALS
NEUTRAL
TERMINAL
GROUND
TERMINAL
MQP240 — diesel generator — rev. #0 (10/05/12)
ꢀ MQP240
Diesel Generator
diMensions
1800 mm/
70.87 in.
1320 mm/
51.97 in.
900 mm/
35.43 in.
900 mm/
35.43 in.
900 mm/
35.43 in.
650 mm/
25.60 in.
450 mm/
17.72 in.
1400 mm/
55.12 in.
2180 mm/85.82 in.
3800 mm/149.61 in.
Weight
Dry Weight
8,645 lbs. (3,920 kg)
Wet Weight
8,865 lbs. (4,020 kg)
Max. Lifting
Point Capacity
16,500 lbs. (7,484 kg)
1115 mm/
43.90 in.
1010 mm/
39.76 in.
585 mm/
23.03 in.
Lifting Point
139 mm/
5.50 in.
640 mm/
25.20 in.
270 mm/
10.63 in.
296 mm/
11.65 in.
1010 mm/
39.76 in.
1115 mm/
43.90 in.
Your Multiquip dealer is:
MultiQuiP
POST OFFICE BOx 6254
CARSON, CA 90749
310-537-3700 • 800-883-2551
FAx: 310-604-3831
E-MAIL: [email protected]
© COPYRIGHT 2012 MULTIQUIP INC.