• Addressable conventional technology
• Maximum temperature 78°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Sealed electronics
Description
The Thermal ROR Detector GD-55000-127 reacts to means of the optional Address Module NG60-1, each
temperature changes within defined periods of time, detector can be addressed individually. With that, the
up to a maximum temperature of 78°C. The intelligent activated detector can also be safely identified directly
evaluation of these data allows the early detection of on the control panel.
spreading fires. The detector complies with Class BR
and can be used up to a room height of 6m.
The detector can be attached to various bases and it
can be protected against theft.
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. By
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 45µA (quiescent)
78°C (maximum-heat component)
max. +65°C
-20°C to +90°C (no condensation or icing)
0 – 95% (no condensation)
100 × 42 (mm)
white
Weight
80g
Approval
VdS G200060
Order number
Order name
242025
Thermal ROR Detector/Conv./65/Apo GD-55000-127
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
GD-55000-127_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
|