• Addressable conventional technology
• Maximum temperature 58°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Thermal ROR Detector ECO1005 reacts to tem-
perature changes within defined periods of time, up
to a maximum temperature of 58°C. The intelligent
evaluation of these data allows the early detection of
spreading fires.
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. By
means of the Address Module NG58-1, each detector
can be addressed individually.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it
can be protected against theft.
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 75µA (quiescent)
58°C (maximum-heat component)
max. +45°C
-30°C to +70°C
5 – 95% (no condensation)
102 × 40.5 (mm)
white
Weight
70g
Approval
VdS G201016
Order number
Order name
242045
Thermal ROR Detector/Conv./1000/SS ECO1005