HEARTH PRODUCTS
KITS AND ACCESSORIES
DIRECT VENT
CHASE TOP SQUARE
750,207M
REV. A 07/2007
VERTICAL TERMINATIONS
INSTALLATION INSTRUCTIONS FOR BLACK - SV4.5CTS-B (CAT. NO. H4716) & SV8CTS-B (CAT. NO. H6179)
AND TERRA COTTA - SV4.5CTS-TC (CAT. NO. H4717) & SV8CTS-TC (CAT. NO. H6180) TERMINATIONS
GENERAL INFORMATION
The SV4.5CTS and SV8CTS series terminations are designed to be
installed on top of locally fabricated chimney enclosure, referred to
herein as a chase. The terminations are designed to be used with tested
and listed Direct Vent pipe systems and manufactured appliances listed
for use with this product. The SV4.5CTS and SV8CTS terminations are
additionally designed and painted to be suitable for use by itself without
surround, providing a beautiful top to a standard chase.
SV4.5CTS
Or SV8CTS
Termination
WARNINGS
Chase Flashing
(Field Fabricated)
This termination is intended to be installed in accordance with the
installation guidelines of the pipe system and appliance it is joined to.
Failure to install this product within those guidelines as well as these
installation instructions can result in damage of property, bodily injury,
or death. The installation must conform with local codes or, with the
national fuel gas code, or ANSI Z223.1.
Pipe
Section
It is highly recommended that this product be installed by a qualified
technician. It ishighlyrecommendedthat thetechnicianbeNFI certified
for gas appliance installations.
APPROVALS AND LISTINGS
The SV4.5CTS and SV8CTS series terminations are tested as a integral
component of the Direct Vent pipe system and may be used with any
manufactured fireplace listed for use with these components. These
terminations are listed for this application by Omni-Test Laboratories.
FOR YOUR SAFETY
When working on ladders, roofs, scaffolding, or any high surface, take
precautions to protect against accidents. Properly secure ladders, wear
safety harnesses and verify all operations are done to OSHA standards.
Also be aware of and avoid any and all electrical wires in or near your
working area.
KIT CONTENTS
1 - Termination
1 - Bag with fifteen (15) stainless steel screws
1 - Instruction Sheet
When working with and around sheet metal, be aware of material edges.
Always wear gloves, safety glass and any other needed protective gear
when working with sheet metal.
Take appropriate precautions when operating power equipment.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 8. Once the termination is positioned, secure it to the chase
flashing using the stainless steel screws provided, through the pre-
punched attachment holes in the attachment tabs of the termination.
Be careful not to over tighten the screws so as to strip out the chase
flashing. In the event of a strip, a larger screw can be used so long
as it is stainless steel. DO NOT use common sheet metal screws, as
they will corrode over time and the termination will no longer be
secure at that point.
VERTICAL VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not super-
sedelocal codesinanyway. InstallSV4.5ventaccordingtothecurrent
National Fuel GasCode, ANSI-Z223.1- latest edition, intheUSAor CAN/
CGA-B149.1 and B149.2 - latest editions in Canada.
Terminatesingleventcapsrelativetobuildingcomponentsaccording to
Figure 4.
Step 9. Once the termination is permanently attached, seal all of the
screw tops with silicone. In order to properly apply the silicone, the
surfaceoftheterminationandscrewsmustbecleananddry. Notsealing
the screws tops will result in water leakage into the chase.
Horizontal Overhang
Vertical
Wall
2 FT
MIN.
2 FT MIN.
Lowest
Discharge
Opening
Vent
Termination
Chase
Flashing
2"
(Max.)
H*
3"
(Max.)
X
Chase
12
Roof Pitch is X/12
Pipe
Section
2 feet
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
2"
(Min.)
(Max.)
1 foot
(Min.)
The vent/air intake termination clearances above the high side of
an angled roof is as shown in the following chart:
Strap
Support
Termination Heights For Vents Above Flat Or
Slopped Roofs Ref. NFPA 54 / ANSI Z223.1, 7.6
H
H
Roof Pitch
(feet) (meters)
Figure 3
Flat to 6/12
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0
0.3
Over 6/12 to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
0.38
0.46
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
MAINTENANCE
As part of an annual inspection, the termination should be checked for
any foreign debris, animal or insect nests, or material of any kind which
may have become lodged in it. The exterior of the termination should be
visually inspected for damage of any kind.
In the event of damage to the termination, it should be replaced with a
new termination. All screw attachments should be checked to insure
they have not loosened over time and they should also be checked for
the water tightness of their silicon seal. The termination must be
removed to clean the chimney. Following cleaning, reinstall the termi-
nation and inspect as detailed in this document.
Figure 4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
The manufacturer reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2006 by Lennox Hearth Products
P/N 750,207M REV. A 07/2007