Philips Work Light WE Series User Manual

WE Series Emergency Lighting WE  
Page 1 of 2  
6 or 12 Volt 18 to 50 Watts NEMA-Rated  
The WE Series is approved for NEMA 3, 3r, 4, 4x, 6, and 12 areas, and is additionally UL listed for wet location areas. The WE Series is ideal for food processing  
and washdown applications.  
13.6”  
(34.5 cm)  
7.1
(18.0
6.5”  
12.0”  
(16.5 cm)  
(30.5 cm)  
Complete Fixture consists of and two lamp heads. Select options and accessories below.  
How to Specify:  
WE  
SERIES  
VOLTAGE  
BATTERY/  
DC WATTAGE  
# OF  
HEADS  
LAMP  
HEADS  
1
12V, Lead Calcium  
36L = 36W  
50L = 50W  
12V, Nickel Cadmium  
50N = 50W  
WE = NEMA-Rated,  
Wet Location Listed  
Emergency Lighting  
Unit  
1 = 6V  
2 = 12V  
6V, Lead Calcium  
18L = 18W  
25L = 25W  
36L = 36W  
50L = 50W  
2 = Two  
1 = One  
6V  
IT8 = 8W  
IT18 = 18W  
IT25 = 25W  
12V  
6V, Nickel Cadmium  
14N = 14W  
18N = 18W  
25N = 25W  
50N = 50W  
IT12 = 12W  
IT18 = 18W  
IT25 = 25W  
NOTES:  
1) Suggested lamp heads  
are listed.  
For additional lamp heads  
see RH specification sheet.  
Options  
Features  
TP = Tamperproof (Requires NTPTOOL, ordered separately)  
T1 = 120 VAC Time Delay  
1. Housing: Constructed of impact resistant, fiberglass reinforced polyes-  
ter. Housing color is gray. Includes two lamp heads externally mounted.  
Choose from 6 or 12 volt NEMA-rated lamp heads  
T2 = 277 VAC Time Delay  
1
IH = Internally Mounted Lamp Heads (battery capacity 25w max.) Specify lamp  
head below:  
S66W = Two 6V, 5.4W White Heads  
S76W = Two 6V, 7W White Heads  
S96W = Two 6V, 9W White Heads  
S66B = Two 6V, 5.4W Black Heads  
2. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-  
state circuitry. Charging system is complete with low voltage disconnect,  
AC lockout, brownout protection, AC indicator lamp and test switch.  
3. Battery: Maintenance free, sealed lead calcium battery has an estimated  
service life of 5 years, and an operating temperature range of 65°F (19°C)  
to 85°F (30°C). Maintenance free, sealed nickel cadmium battery has an  
estimated service life of 10 years, and an operating temperature range of  
20°F (-7°C) to 95°F (35°C).  
S76B = Two 6V, 7W Black Heads  
S96B = Two 6V, 9W Black Heads  
EXAMPLE: WE118L2S96BIH  
Multiple option configurations may void UL listing. Consult factory for specifics.  
4. Input Power Requirements: 120 VAC - 0.15 amps, 18 watts; 277 VAC -  
0.07 amps, 18 watts  
1) Internal heads only available with “S” type heads  
Code Compliance  
Job Information  
Type:  
UL (Suitable for Wet or Damp Locations)  
NSF/ANSI Standard 2 Food Equipment.  
NEMA-Rated for use in 3, 3r, 4, 4x, 6 or 12 areas.  
Job Name:  
Cat. No.:  
Accessories  
EMF = External Mounting Feet  
NTPTOOL = Tamperproof Screwdriver  
PCS1 = Polycarbonate Vandal Shield  
WG5 = Wire Guard  
Lamp(s):  
Notes:  
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710  
We reserve the right to change details of design, materials and finish.  
Lightolier is a Philips group brand  
 

Peavey Microphone LX 20S User Manual
Philips Cordless Telephone CD1550B User Manual
Philips Electric Shaver 4401 User Manual
Philips Universal Remote SRU4105 User Manual
Philips Universal Remote TSU9600 User Manual
Planet Technology Network Router VC 200M User Manual
Polaroid MP3 Player PMP280C 4 User Manual
Poulan Trimmer 545186848 User Manual
Powermate Portable Generator PC049650417 User Manual
ProForm Treadmill PFTL72582 User Manual