MODEL 13000 PTOG
ITEM # 165929
Power Take-Off Generator
P r o v e n P e r f o r m a n c e
M165929A
OWNER’S MANUAL
00293
13000 PTOG
Any Questions, Comments, or Problems?
Call Customer Service at 1-800-270-0810
Hours: Monday - Friday 7:30 AM to 5:30 PM
Saturday 7:30 to 11:30 AM CST
SPECIFICATIONS
Item Number
Maximum Output
Continuous Output
Voltage
#165929
13000 Watts (W)
12000 Watts (W)
120 / 240 Volt (V)
Phase
Single phase (4-wire)
Frequency
59.0-63.0 Hertz (Hz)
Power Factor
Minimum PTO HP
Input Shaft
100 %
24 HP at 540 RPM
1 3/8” Diameter, 6 spline
120VReceptacle
(2) 20 Amp (A) duplex (NEMA5-20R)
30 Amp (A) twistlock (NEMAL5-30R)
50 Amp (A) Straight blade (NEMA14-50R)
(2) 20 Amp (A) thermal, push to reset style
30 Amp (A) thermal, push to reset style
(2) 40 Amp (A) thermal, push to reset style
120/240VReceptacle
Circuit Breaker
Gear Box
Gear Ratio
Gear Oil
Oil Capacity
Dimensions
Length
Width
Height
Gross Weight
1:7
SAE 80W-90
.86 Qt. (.82 L)
28.38” (72.1 cm)
14.25” (36.2 cm)
12.50” (31.1 cm)
127 lb. (57.7kg)
ANSI SAFETY DEFINITIONS
DANGER indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury. This signal word is to be limited to the
most extreme situations.
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in a death or serious injury.
CAUTION indicates a potentially hazardous situation, which if not avoided,
may result in minor or moderate injury. It may also be used to alert against
unsafe practices.
2
MACHINE COMPONENT IDENTIFICATION
00294
Figure 1 (Ref. 1-10)
Ref. Description
Ref. Description
1
2
3
4
5
6
7
8
50A Circuit Breakers
10
11
12
13
14
15
16
17
120/240V 50A Receptacle
Shield
Gear Box
Grounding Screw
Mounting Holes
Fan Vents
Oil Level Sight
Breather/Oil Fill Plug
30A Circuit Breaker
20A Circuit Breakers
Warning Decals
1 3/8”, 6 Spline Input Shaft
Oil Drain Plug
Voltmeter
120V 20A Duplex
Receptacles
9
120V 30A Twistlock
Receptacle
3
receptacle accepts NEMA plug number L5-30P,
which is supplied with the generator.
GENERATOR FEATURES
Reference 10 - 120/240V Receptacle. This
straight blade receptacle is 120/240V 50A. This
receptacle accepts a NEMA plug number 14-50P.
References 1-3 Circuit Breakers.
• Reference 1 - two 50A push-to-reset circuit
breakers.
• Reference 2 - one 30A push-to-reset circuit
breaker.
Reference 3 - two 20A push-to-reset circuit
breakers.
References 4 - Warning Decals. Read and
ALWAYS use grounded male plugs.
The
neutral line of the generator is mechanically
grounded to the frame. Matching NEMA male
plugs must always be used.
References 11 - Shield. Plastic implement
shield. NEVER operate generator without shield in
place.
Reference 12 - Gear Box. Cast iron frame. 1:7
gear ratio.
Reference 13 - Grounding Screw. Ground the
generator via the ground screw, to a copper pipe or
rod that is driven into moist soil.
•
follow all warnings.
References 5 - 1 3/8” Diameter 6 Spline Input
Shaft. 540 RPM. PTO driveline is available from
Northern, Item #165936.
References 6 - Oil Drain Plug. Change oil
after the first 50 hours of use, then after every 500
hours.
Reference 14 - Mounting Holes. Use these
three locations to mount the generator head in
place with 7/16” grade 5 bolts. Mounting plates
(item #165935) for mounting generator to a cement
pad are available through Northern and the
NorthStar parts catalog.
Reference 15 - Fan Vents. Never block the
vent slots or insert objects through the slots. The
closest object should be at least 3 feet away from
the vents.
References 7 - Voltmeter. Voltmeter needle
should be in green area during all generator load
conditions. The black line in the center on the
green area indicates 120V.
During no load
conditions, the needle should be at or above the
black line.
References 8-9 120V Receptacles.
•
Reference 8 - 120V Receptacle.
The
generator has a control panel with two 120V 20A
straight blade receptacle duplexes (two receptacles
Reference 16 - Oil Level Sight. When oil is
even with the red dot, the oil level is correct. Check
in
a
common housing). National Electrical
Manufacturer’s Association (NEMA) number is 5-
20R.
oil level daily. Sight is mounted on the gear box
00295
service panel. If panel is removed for whatever
eal using Dow Corning sealant #732.
•
Reference 9 - This twistlock receptacle is a
120V 30A receptacle, NEMA number L5-30R.
Figure 2 (Ref. 10-16)
4
Reference 17 - Breather/Oil Fill Plug. Use
SAE 90 gear oil. Maintain the correct oil level.
Over filling can cause the oil to over heat and
damage seals and bearings. The gear box is
shipped with temperary plastic plug, remove and
replace with the metal breather plug that is in the
manual bag.
ALWAYS provide adequate ventilation. Do not
operate generator in any enclosed or narrow space.
Engines consume oxygen and give off deadly
carbon monoxide, a poisonous gas.
Improper
ventilation will cause damage to generator and
possible injury to people.
ALWAYS remove all oil or gasoline deposits
and accumulated dirt from generator and
immediate area. Keep generator head and engine
clean.
INTRODUCTION
ALWAYS wear ear protection while operating
generator.
ALWAYS keep area around generator clean.
NEVER operate the generator without proper
guarding.
NEVER operate the generator continuously
when PTO driveline is at angle greater than 15°
both horizontally and vertically .
NEVER operate the generator while wearing
loose fitting clothing such as neckties, scarves or
untucked shirts.
Before attempting to mount your generator,
thoroughly study the instructions and cautions in this
manual to assure you are fully acquainted with the
operation of all components of this generator. Proper
preparation, operation and maintenance will result
in operator safety, best performance and long life of
the generator. NorthStar is constantly improving its
products. The specifications outlined herein are
subject to change without prior notice or obligation.
The purchaser and/or user assumes liability of any
modification and/or alterations on this equipment
from original design and manufacture. Before using,
the user shall determine the suitability of this product
for its intended use and assumes liability therein.
NEVER operate the generator, or handle any
electrical equipment while standing in water, while
barefoot, while hands are wet or while in the rain or
snow. Electric shock may result.
NEVER operate the generator under the
following conditions:
RULES FOR SAFE OPERATIONS
A. Excessive change in engine speed, slow
or fast.
B. Overheating in load connecting devices.
C. Sparking or arcs from generator.
D. Loss of electrical output.
Safety precautions are essential when operating
this generator. Respectful and cautious operation
will considerably lessen the possibilities of
personal injury. This manual will warn of specific
personal injury potential, and these will be
designated by the symbol:
a
E. Damaged receptacles.
F. Engine misfire.
G. Excessive vibration.
H. Enclosed compartments, or confined areas.
I. Flame or smoke.
J. Rain, snow or wet conditions.
K. Operator non-attendance.
L. Without proper guarding in place.
WARNING This generator is equipped
with a grounding screw, located on the generator
frame for your protection. Always complete the
grounding path from the generator to a copper
pipe/rod that is driven into moist earth, to prevent
electrical shock.
WARNING Keep fire extinguisher close
by your generator and be familiar with how to use
it. Consult your local fire department for correct
extinguisher type.
ALWAYS use electrical cords that are in good
condition.
Worn, bare, frayed or otherwise
DANGER Remember, exhaust fumes are
deadly carbon monoxide, a poisonous gas and
must be vented to the outside where there are no
people. Cooling air of sufficient amounts must be
brought in and exhausted out to ensure proper
cooling of the engine and generator.
damaged cords can cause electric shock.
ALWAYS use a ground fault circuit interrupter
(GFCI) in damp or highly electrical conductive
areas and on construction job sites to prevent
electric shock.
ALWAYS remove PTO driveline before working
on the generator.
INSTALLATION
5
Choose a location where the generator will not
be exposed to rain, snow or direct sunlight.
Common places for mounting your PTO generator
are to a trailer or a cement slab. However you
choose to mount the generator, make sure it can
get as close to the load as possible. This will make
using the generator more convenient and reduce
voltage drop.
The installation site must be free from water,
moisture, or dust. Foreign matters, such as dust, dirt,
sand, lint, or abrasive materials can cause damage
After the the generator is firmly mounted ,
attach the PTO driveline to the generator then the
tractor. Use a synchronized PTO driveline rated at
24 HP minimum.
if allowed inside the generator.
All electrical
components should be protected from excessive
moisture or the insulation system will deteriorate
and result in grounding or shorting out of the
generating system.
When trailer mounting the generator select a
trailer that is wide enough to withstand the torque
of start-up and loading torque. Wheels that are not
spaced properly could cause the trailer to tip over.
The constant vibration of the generator can cause
metal fatigue of the trailer base if the steel used is
not thick enough.
DANGER Always have proper guarding
of rotating parts.
Failure to guard the power
transmission mechanisms may result in serious
injury or death.
While seated on the tractor and the engine at
idle, engage the PTO. Slowly increase the throttle
until the needle in the generator voltmeter is at or
above the black line in the green area. A load can
now be applied to the generator. Remember to
DANGER Trailer may tip over and cause
00345
stay clear of the rotating PTO driveline. From the
serious injury or death.
Never stand near an
tractor seat re-adjust the speed until the needle on
the generator voltmeter is close to the black line in
the green area. If the needle will not rise to the
green area no matter what the engine speed, the
generator is either overloaded or there is a
problem. Use the troubleshooting guide at the end
of the manual for assistance with possible problems.
Before each use check the gear box oil level.
Use SAE gear oil and fill to the dot on the sight
glass.
operating PTO generator.
When mounting the generator on a cement slab
use the optional mount kit (item #165935),
available in the Northern catalog and the NorthStar
parts catalog. The kit comes with two mounting
plates and three grade 5, 7/16-14 bolts. Use grade
5 3/8” anchor bolts to mount plates to the concrete.
If the control box is not located on the correct
side for your application, it can be rotated to the
opposite side. First remove the fan vents, then
remove the four drive end bracket bolts. Remove
securing stud cap, loosen the securing stud nut.
Rotate the drive end bracket 180°, re-torque bolts to
17 lb•ft. Re-torque securing stud nut to 88•ft.
00346
Reinstall the fan vents. Remove the four screws at
the base of control box, rotate the control box 180°.
The voltmeter is now on the back of the machine
instead of the front. See below for terminology.
6
STARTING ELECTRIC MOTORS
Electric motors require much more current
(amps) to start than to run.
Some motors,
particularly low cost split-phase motors, are very
hard to start and require 5 to 7 times more current
to start than to run. Capacitor motors are easier to
start and usually require 2 to 4 times as much
current to start than to run. Repulsion Induction
motors are the easiest to start and require 1.5 to 2.5
times as much to start than to run.
Most fractional motors take about the same
amount of current to run them whether they are of
Repulsion-Induction (RI), Capacitor (Cap), or Split-
Phase (SP) type. The following chart shows the
approximate current required to start and run
various types and sizes of 120 volt 60 cycle electric
motors under various conditions.
LOAD APPLICATION
It is important to determine the total electrical
load before it is connected to the generator. The
two major factors in determining the life of a
generator head are: heat build up, caused by
overloading
the
generator
and
corrosive
120V,
60
Hz
Starting Amps
contaminants, that attack the wiring insulation. If
the generator is overloaded, the wires become
excessively hot and cause the insulation to break
down, reducing its ability to resist corrosive
contaminants. Over time the effectiveness of the
insulation is eliminated and a dead short can result.
Always compare the generator nameplate data
with that of the equipment to be used to ensure that
watts, volts, amperage, and frequency requirements
are suitable for operating equipment. The wattage
listed on the equipment nameplate is its rated
output. However, some equipment may require
three to ten times more wattage than its rating on
the nameplate, as the wattage is influenced by the
equipment efficiency, power factor and starting
Motors
Hp motor Running RI type
Watts
Cap
type
SP
type
1/6
1/4
1/3
1/2
1
1 1/2
2
3
525
700
875
1175
1925
2400
2900
4075
6750
7-11
9-15
9-18
12-23
14-29
20-40
32-64
40-80
48-96
68-136
112-224
16-22
22-32
26-35
NA
NA
NA
NA
NA
NA
11-18
15-25
24-40
30-50
36-60
51-85
84-140
5
The figures given above are for an average
load such as a blower or fan. If the electric motor is
connected to a hard starting load such as an air
compressor, it will require more starting current. If it
is connected to a light load or no load such as a
power saw, it will require less starting current. The
exact requirement will also vary with the brand or
design of the motor.
00402
system.
NOTE:
If wattage is not given o
equipment nameplate, approximate wattage may
be determined by multiplying nameplate voltage
by nameplate amperage.
VOLTS X AMPS = WATTS
Example: 120V
600W
X 5A
=
Generators respond to severe overloading
differently than the power line. When overloaded,
the engine is not able to supply enough power to
bring the electric motor up to operating speed. The
generator responds to the high initial starting
current, but the engine speed drops sharply. The
When connecting a resistive load such as
incandescent lights, heaters or common electric
power tools, a capacity of up to the generator full
rated wattage output can be used.
When connecting a resistive-inductive load such
as a fluorescent or mercury light, transformers or
inductive coils, a capacity of up to 0.6 times the
generator’s full rated output can be used.
overload may stall the engine.
operate at very low speeds, the electric motor starter
winding will burn out in a short time. The
If allowed to
Always allow the generator to reach operating
speed before a load is applied.
generator head winding might also be damaged.
Running the generator under these conditions
may result in damage to the generator stator as well
7
as the electric motor windings. Because the heavy
surge of current is required for only an instant, the
generator will not be damaged if it can bring the
motor up to speed in a few seconds. If difficulties in
starting a motor are experienced, turn off all other
electrical loads and if possible reduce the load on
the electric motor.
Freezer
Furnace Fan (1/3 HP)
Hair Dryer
800 (b)
1200 (a)
1200
1100
875
Hand Drill (1”)
Hand Drill (1/2”)
Hand Drill (3/8”)
Hand Drill (1/4”)
Hedge Trimmer
Home Computer
Impact Wrench
500
250
450
150
EXTENSION CORDS
500
Jet Pump
Lawn Mower
Light Bulb
Microwave Oven
Milk Cooler
Oil Burner on Furnace
Oil Fired Space Htr (140,000 Btu)
Oil Fired Space Htr (85,000 Btu)
Oil Fired Space Htr (30,000 Btu)
Oven
Paint Sprayer, Airless (1/3 HP)
Paint Sprayer, Airless (handheld)
Radio
800 (a)
1200
100
700
1100 (a)
300
400
225
150
4500
600 (a)
150
200
600 (b)
200
2800 (a)
2000 (a)
1500 (a)
600 (a)
2000 (a)
500
1000
250
70
When electric power is to be provided to various
loads at some distance from the generator,
extension cords can be used. These cords should
be sized to allow for distance in length and
amperage so that the voltage drop between the set
and point of use is held to a minimum.
Current/Powe Maximum Extension Cord Length
r
Amps Load
#10
Ga.
#12
Ga.
#14
Ga.
#16
Ga.
at
(watts)
240V
Cord
Cord
Cord
Cord
10
20
30
40
50
2400
4800
7200
9600
12000
250’
125’
60’
30’
15’
150’
75’
35’
15’
*
100’
50’
25’
10’
*
75’
25’
10’
*
Refrigerator
Slow Cooker
Submersible Pump (1-1/2 HP)
Submersible Pump (1 HP)
Submersible Pump (1/2 HP)
Sump Pump
Table Saw (10”)
Television
Toaster
Vacuum cleaner
VCR
*
*Not recommended
CAUTION: Equipment damage can result from
the low voltage caused by using an extension cord
with a small wire size.
Use this chart to estimate the total load on your
generator.
Water Heater
Weed Trimmer
3000
500
For Determining Generator Load Requirements
(a) Hard-starting motors require 3 to 5 times the
rated running watts.
(b) These loads may require up to 15 minutes to
restart due to its normal build up of compressor
head pressure.
NOTE: For extremely hard to start loads such as
air conditioners and air compressors, consult the
equipment dealer to determine the maximum
wattage.
Device
Running Watts
1700 (a)
500
Air Conditioner (12,000 Btu)
Battery Charger (20 Amp)
Belt Sander (3”)
1000
Chain Saw
1200
Circular Saw (6-1/2”)
Coffee Maker
900
1000
Compressor (1 HP)
Compressor (3/4 HP)
2000 (a)
1800 (a)
Generator Load Requirements Continued
PRE-START UP PREPARATIONS
Compressor (1/2 HP)
Curling Iron
1400 (a)
700
Your generator has been thoroughly tested prior
to shipment from the factory. However, damage
can occur during shipping, so be sure to check for
damaged parts, loose or missing nuts and bolts. If
the these problems occur, call Customer Service at
1-800-270-0810.
Dishwasher
Edge Trimmer
1200
500
Electric Nail Gun
Electric Range (one element)
Electric Skillet
1200
1500
1250
8
GENERATOR CARE
GROUNDING - All units must be grounded.
Drive a 3/4” or 1” copper pipe or rod into the ground
The generator head is a two pole, 3600 RPM,
60 Hz, brushless, revolving field and synchronous
type with two sealed radial bearings.
Proper care and maintenance are necessary to
ensure a long trouble free life.
close to the generator.
penetrate moist earth.
The pipe/rod must
Connect an approved
ground clamp to the pipe. Run a 8 gauge wire
from the clamp to the generator ground screw. Do
not connect to a water pipe or a ground used by a
radio system.
Exercising The Generator - The generator
should be operated every four weeks. This is
accomplished by starting the engine and applying
a load for 15 minutes. This will dry out any
moisture that has accumulated in the windings. If
left, this moisture can cause corrosion in the
winding. Frequent operation of the generator will
also ensure that the set is operating properly should
it be needed in an emergency.
Generator Maintenance - The generator head
is brushless and maintenance free. Any major
generator service including the installation or
replacement of parts should be performed only by a
qualified electrical service technician. USE ONLY
NorthStar APPROVED REPAIR PARTS AVAILABLE
AT 1-800-270-0810.
A. Bearing - The bearings used in this generator
are a heavy duty, sealed ball bearing type. They
require no maintenance or lubrication.
B. Receptacles - Quality receptacles have been
utilized. If a receptacle should become cracked or
otherwise damaged, replace it. Using cracked or
damaged receptacles can be both dangerous to the
operator and destructive to the equipment.
OPERATING SPEED
The generator must be run at the correct speed
in order to produce the proper electrical voltage
and frequency.
The output voltage should be checked to
ensure the generator is working properly subsequent
to connecting a load to the generator. Failure to
do so could result in damage to equipment
plugged into the unit and possible injury to the
individual.
All engines have a tendency to slow down when
a load is applied. When the electrical load is
connected to the generator, the engine is more
heavily loaded, and as a result the speed drops
slightly. This slight decrease in speed, together
with the voltage drop within the generator itself,
results in a slightly lower voltage when the
generator is loaded to its full capacity than when it
is running with no load. The slight variation has no
appreciable effect in the operation of motors, lights
and most appliances. Electronic equipment and
clocks will be effected if correct RPM is not
maintained. See Load vs. Output chart
WARNING, Stand-by Operation
If your generator is to be used as a standby
electric power source in case of utility failure, it
must be installed by a registered and licensed
electrician and in compliance with all applicable
state and local electrical codes. Also, local Fire
Departments must be consulted concerning proper
and safe handling procedures for gasoline. NEVER
connect any generator to any existing electrical
system without an isolating, UL approved transfer
switch, installed by a licensed electrician.
Load
Output
Frequency
(Hz)
Percent of
Generator
Output
Speed
(RPM)
Generator
voltage at
120V
Receptacle
0 %
50 %
100 %
3780
3600
3480
63.0
60.0
58.0
125V
122V
118V
Output voltage should be checked periodically
to ensure continued proper operation of the
generating plant and appliances, it can be checked
with a portable meter. Frequency can be checked
by using an electric clock with a sweep second
hand. Timed against a wrist watch or a stop watch
the clock should be correct within +/- 2 seconds per
minute. All speed setting adjustments should be
done by a qualified technician.
9
TROUBLESHOOTING
Problem
Possible Causes
Possible Remedies
Voltage too low.
a)
b)
a)
Engine speed too slow.
Generator is overloaded.
Defective load connected to
a)
b)
Increase tractor RPMs.
Reduce the load. (See Load
Application section of this manual.)
Circuit breaker trips.
a)
b)
Disconnect load.
Replace receptacle.
generator.
b)
Defective receptacle.
c) Reduce the load. (See Load
c) Generator overloaded.
Application section of this manual.)
d)
Contact Customer Service for
d) Defective circuit breaker.
the nearest service center.
Voltage too high.
a)
a)
b)
Engine speed too high.
Generator is overloaded.
Insufficient ventilation.
a)
Contact Customer Service for
the nearest service center.
a)
Application section of this manual.)
b)
Generator
overheating.
Reduce the load. (See Load
Make sure there is at least 3
feet of clearance on all sides of
generator.
No output voltage.
a)
Defective load connected to
a)
b)
Disconnect load.
Replace/tighten wire.
generator.
b)
Broken or loose wire.
c) Replace receptacle.
d)
Contact Customer Service for
c) Defective receptacle.
the nearest service center.
d)
Defective stator.
e)
Contact Customer Service for
the nearest service center.
f) Contact Customer Service for the
nearest service center.
e)
Defective rotor.
f) Defective capacitor.
g)
Contact Customer Service for
the nearest service center.
h) Increase tractor RPMs.
I) Engage PTO.
g)
Defective circuit breaker.
h) Engine speed too slow.
I) PTO not engaged.
j) Contact Customer Service for the
nearest service center.
j) Gear box is malfunctioning.
Excessive gear box
noise.
a)
Defective bearing.
a)
Contact Customer Service for
the nearest service center.
b) Defective gear.
b)
Contact Customer Service for
the nearest service center.
c) No or low gear oil.
c) Fill gear box to oil level sight.
d) PTO driveline is operating at an angle d) Repostition the tractor or generator
of greater than 15°.
so the angle is reduced to less than 15°
both vertically and horizontally.
e) Disassemble PTO driveline and
reassemble with CV joints
e) Unsynchronized PTO driveline.
synchronized.
10
|