National Instruments Network Card NI 9852 User Manual

OPERATING INSTRUCTIONS  
NI 9852  
2-Port, Low-Speed/Fault-Tolerant CAN Module  
 
Safety Guidelines for Hazardous Locations  
The NI 9852 is suitable for use in Class I, Division 2, Groups A, B,  
C, D, and T4 hazardous locations; Class 1, Zone 2, AEx nA II T4  
and Ex nA II T4 hazardous locations; and nonhazardous locations  
only. Follow these guidelines if you are installing the NI 9852 in a  
potentially explosive environment. Not following these guidelines  
may result in serious injury or death.  
Caution Do not disconnect I/O-side wires or connectors  
unless power has been switched off or the area is known  
to be nonhazardous.  
Caution Do not remove modules unless power has been  
switched off or the area is known to be nonhazardous.  
Caution Substitution of components may impair  
suitability for Class I, Division 2.  
Caution For Zone 2 applications, install the  
CompactRIO system in an enclosure rated to at least  
IP 54 as defined by IEC 60529 and EN 60529.  
© National Instruments Corp.  
3
NI 9852 Operating Instructions  
 
Caution For Zone 2 applications, install a protection  
device between the CAN signals and the NI 9852 CAN  
pins. The device must prevent the CAN Port-to-COM  
voltage from exceeding 55 V if there is a transient  
overvoltage condition.  
Special Conditions for Hazardous Locations Use in Europe  
This equipment has been evaluated as EEx nA II T4 equipment  
under DEMKO Certificate No. 03 ATEX 0324020X. Each module  
is marked  
locations.  
II 3G and is suitable for use in Zone 2 hazardous  
Wiring the NI 9852  
The NI 9852 has two 9-pin male D-Sub connectors that provide  
connections to a CAN bus. Each port on the NI 9852 has pins for  
CAN_H and CAN_L, to which you connect the CAN bus signals.  
These signals should be connected using twisted-pair cable.  
NI 9852 Operating Instructions  
4
ni.com  
 
Each port has two isolated common pins (COM) that are internally  
connected to the isolated reference of the module and serve as the  
reference ground for CAN_H and CAN_L. Connect the CAN bus  
reference ground (sometimes referred to as CAN_V–) to the COM  
pin. Each port also has an optional shield pin, SHLD, that can be  
connected to a shielded CAN cable. Connecting SHLD may  
improve signal integrity and EMC performance in a noisy  
environment.  
Both of the ports on the NI 9852 require an external power supply  
of +8 V to +36 V to operate. Supply power from the CAN bus to  
the VSUP0 pin on CAN0, and the VSUP1 pin on CAN1.  
Pinouts for CAN0 and CAN1 of the NI 9852 are listed in Table 1  
and Table 2.  
© National Instruments Corp.  
5
NI 9852 Operating Instructions  
 
Table 1. Pin Assignments for CAN0  
Connector  
Pin  
Signal  
1
2
3
4
5
6
7
8
9
No Connection (NC)  
CAN_L  
COM0  
NC  
1
2
3
4
5
6
7
8
9
SHLD  
COM0  
CAN_H  
NC  
VSUP0  
NI 9852 Operating Instructions  
6
ni.com  
 
 
Table 2. Pin Assignments for CAN1  
Connector  
Pin  
Signal  
1
2
3
4
5
6
7
8
9
No Connection (NC)  
CAN_L  
COM1  
NC  
1
2
3
4
5
6
7
8
9
SHLD  
COM1  
CAN_H  
NC  
VSUP1  
© National Instruments Corp.  
7
NI 9852 Operating Instructions  
 
 
CAN Bus Topology and Termination  
A CAN bus consists of two or more CAN nodes cabled together.  
The CAN_H and CAN_L pins of each node are connected to the  
main CAN bus cable through a short connection known as a “stub.”  
The pair of signal wires, CAN_H and CAN_L constitutes a  
transmission line. Every device on a low-speed/fault-tolerant CAN  
network requires a termination resistor for each CAN data line:  
RRTH for CAN_H and RRTL for CAN_L.  
Figure 1 shows a simplified diagram of a low-speed/fault-tolerant  
CAN bus with termination resistor placements.  
NI 9852 Operating Instructions  
8
ni.com  
 
Low-speed/Fault-Tolerant  
CAN Device  
Low-speed/Fault-Tolerant  
CAN Device  
Low-speed/Fault-Tolerant  
CAN Device  
RTL CAN_L  
RTH CAN_H  
RTL CAN_L  
RTH CAN_H  
RTL CAN_L  
RTH CAN_H  
CAN_H  
CAN_L  
Figure 1. CAN Bus Topology and Termination Resistor Locations  
Connecting a CAN Bus to the NI 9852  
Each port of the NI 9852 can be connected to any location on a  
CAN bus. Figure 2 shows one example of the connection of CAN0  
of the NI 9852 directly to one CAN node, and CAN1 directly to  
another CAN node. CAN0 and CAN1 require an external power  
supply on the CAN bus.  
© National Instruments Corp.  
9
NI 9852 Operating Instructions  
 
 
(SHLD)  
CAN_H  
CAN_L  
(SHLD)  
CAN_H  
CAN_L  
CAN  
Cable  
CAN0  
(With  
V
V
sup0  
sup0  
Optional  
Shield)  
+
COM0  
COM0  
External  
Power  
Supply  
NI 9852  
(SHLD)  
CAN_H  
CAN_L  
(SHLD)  
CAN_H  
CAN_L  
CAN  
Cable  
(With  
Optional  
Shield)  
CAN1  
V
V
sup1  
sup1  
+
COM1  
COM1  
External  
Power  
Supply  
Figure 2. Connecting Both Ports of the NI 9852 to CAN Buses  
NI 9852 Operating Instructions  
10  
ni.com  
 
 
Cabling Requirements for NI 9852  
This section deals with cabling specifications, termination  
resistors, cable lengths, and the number of CAN nodes that can  
exist in a system.  
Cable Specifications  
Cables should meet the physical medium requirements specified in  
ISO 11898, shown in Table 3. Belden cable (3084A) meets all of  
those requirements, and should be suitable for most applications.  
Table 3. Specifications for Characteristics of a CAN_H and CAN_L Pair of  
Wires  
Characteristic  
Value  
Length-related resistance 90 mΩ/m nominal  
Length-related  
30 pF/m nominal  
capacitance:  
CAN_L and ground,  
CAN_H and ground,  
CAN_L and CAN_H  
© National Instruments Corp.  
11  
NI 9852 Operating Instructions  
 
 
Determining the Necessary Termination Resistance  
for the Board  
Unlike High-Speed CAN, Low-Speed/Fault-Tolerant CAN  
requires termination at the Low-Speed/Fault-Tolerant CAN  
transceiver instead of on the cable itself. Termination requires  
two resistors, RTH for CAN_H and RTL for CAN_L. This  
configuration allows the Philips Fault-Tolerant CAN transceiver to  
detect and recover from bus faults. It is important to determine the  
overall termination of the existing network, or the termination of  
the individual device, before connecting it to a  
Low-Speed/Fault-Tolerant port. Philips recommends an overall  
RTH and RTL termination of 100 to 500 Ω (each) for a properly  
terminated low-speed network.  
Termination on the low-speed/fault-tolerant ports of the NI 9852 is  
set through the NI 985x software to either 1 kΩ or 5 kΩ.  
NI 9852 Operating Instructions  
12  
ni.com  
 
Number of CAN Nodes  
The maximum number of nodes depends on the electrical  
characteristics of the nodes on the network. If all of the nodes meet  
the requirements of Low-Speed/Fault-Tolerant CAN, up to  
32 nodes may be connected to the bus.  
NI 9852 Hardware Overview  
The NI 9852 has two full-featured, independent CAN ports that are  
isolated from each other, and from the other modules in the system.  
Each port of the NI 9852 has a Philips SJA1000 CAN controller  
that is CAN 2.0B-compatible and fully supports both 11-bit  
and 29-bit identifiers. Each port also has a Philips TJA1054A  
Low-Speed/Fault-Tolerant CAN that is fully compatible with the  
ISO 11898 standard and supports baud rates up to 125 Kbps.  
© National Instruments Corp.  
13  
NI 9852 Operating Instructions  
 
VSUP0  
+
_
Ext Pwr  
Supply 0  
+5 V  
Reg  
COM0  
CAN_H  
Rx  
Tx  
Rx  
Tx  
CAN  
Transceiver  
CAN  
Controller  
CAN_L  
CAN0  
VSUP1  
+
_
+5 V  
Reg  
Ext Pwr  
Supply 1  
COM1  
CAN_H  
Rx  
Tx  
Rx  
Tx  
CAN  
Transceiver  
CAN  
Controller  
CAN_L  
CAN1  
Figure 3. NI 9852 Hardware Overview  
NI 9852 Operating Instructions  
14  
ni.com  
 
Sleep Mode (CompactRIO Only)  
You can enable sleep mode for the CompactRIO system in  
software. In sleep mode, the system consumes less power and may  
dissipate less heat. Typically, when a system is in sleep mode, you  
cannot communicate with the modules. Refer to the Specifications  
section for more information about power consumption and  
thermal dissipation.  
This system sleep mode should not be confused with the NI 9852  
Transceiver Mode Sleep property, which sets only the CAN port to  
sleep mode. Refer to the FPGA Module topic in LabVIEW Help for  
more information on the Transceiver Mode property.  
© National Instruments Corp.  
15  
NI 9852 Operating Instructions  
 
Specifications  
The following specifications are typical for the range –40 to 70 °C  
unless otherwise noted.  
Low-Speed/Fault-Tolerant CAN Characteristics  
Transceiver........................................Philips TJA1054A  
Max baud rate ...................................125 Kbps  
CAN_H, CAN_L bus lines  
voltage...............................................27 to +40 VDC  
Supply voltage range (VSUP0/VSUP1  
)
CAN0 .........................................+8 to +36 VDC  
CAN1 .........................................+8 to +36 VDC  
RRTH............................................1.11 kΩ 0.5% or  
4.99 kΩ 0.5%  
RRTL ............................................1.11 kΩ 0.5% or  
4.99 kΩ 0.5%  
MTBF ...............................................1,052,836 hours at 25 °C;  
Bellcore Issue 6, Method 1,  
Case 3, Limited Part Stress  
Method  
NI 9852 Operating Instructions  
16  
ni.com  
 
 
Note Contact NI for Bellcore MTBF specifications at  
other temperatures or for MIL-HDBK-217F  
specifications.  
Power Requirements  
Power consumption from chassis  
Active mode  
Transmitting.........................400 mW max  
Receiving .............................400 mW max  
Sleep mode .................................25 μW max  
Thermal dissipation (at 70 °C)  
Active mode ...............................1.5 W max  
Sleep mode .................................1.2 W max  
Physical Characteristics  
If you need to clean the module, wipe it with a dry towel.  
Weight...............................................Approx. 144 g (5.0 oz)  
© National Instruments Corp.  
17  
NI 9852 Operating Instructions  
 
Safety  
Maximum Voltage1  
Connect only voltages that are within these limits.  
Port-to-COM.....................................27 to +40 VDC max,  
Measurement Category I  
Measurement Category I is for measurements performed on  
circuits not directly connected to the electrical distribution system  
referred to as MAINS voltage. MAINS is a hazardous live electrical  
supply system that powers equipment. This category is for  
measurements of voltages from specially protected secondary  
circuits. Such voltage measurements include signal levels, special  
equipment, limited-energy parts of equipment, circuits powered by  
regulated low-voltage sources, and electronics.  
Caution Do not connect to signals or use for  
measurements within Measurement Categories II, III,  
or IV.  
1
The maximum voltage that can be applied or output between any port or VSUP  
terminal and a COM terminal without creating a safety hazard.  
NI 9852 Operating Instructions  
18  
ni.com  
 
Isolation Voltages  
Port-to-port  
Withstand....................................500 Vrms, 5 s  
Continuous .................................60 VDC,  
Measurement Category I  
Port-to-earth ground  
Withstand....................................500 Vrms, 5 s  
Continuous .................................60 VDC,  
Measurement Category I  
Safety Standards  
The NI 9852 is designed to meet the requirements of the following  
standards of safety for electrical equipment for measurement,  
control, and laboratory use:  
IEC 61010-1, EN 61010-1  
UL 61010-1, CSA 61010-1  
Note For UL and other safety certifications, refer to the  
product label, or visit ni.com/certification, search  
by model number or product line, and click the  
appropriate link in the Certification column.  
© National Instruments Corp.  
19  
NI 9852 Operating Instructions  
 
Hazardous Locations  
U.S. (UL) ..........................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2, AEx nA  
II T4  
Canada (C-UL) .................................Class I, Division 2,  
Groups A, B, C, D, T4;  
Class I, Zone 2, Ex nA  
II T4  
Europe (DEMKO).............................EEx nA II T4  
Environmental  
CompactRIO modules are intended for indoor use only. For  
outdoor use, mount the CompactRIO system in a suitably rated  
enclosure. Refer to the installation instructions for the chassis you  
are using for more information about meeting these specifications.  
Operating temperature ......................40 to 70 °C  
Storage temperature..........................40 to 85 °C  
Ingress protection..............................IP 40  
Operating humidity...........................10 to 90% RH,  
noncondensing  
NI 9852 Operating Instructions  
20  
ni.com  
 
Storage humidity...............................5 to 95% RH,  
noncondensing  
Maximum altitude.............................2,000 m  
Pollution Degree (IEC 60664)..........2  
Shock and Vibration  
To meet these specifications, you must panel mount the  
CompactRIO system.  
Operating vibration,  
random (IEC 60068-2-64) ................5 grms, 10 to 500 Hz  
Operating shock  
(IEC 60068-2-27)..............................30 g, 11 ms half sine,  
50 g, 3 ms half sine,  
18 shocks at 6 orientations  
Operating vibration,  
sinusoidal (IEC 60068-2-6) ..............5 g, 10 to 500 Hz  
© National Instruments Corp.  
21  
NI 9852 Operating Instructions  
 
Electromagnetic Compatibility  
This product is designed to meet the requirements of the following  
standards of EMC for electical equipment for measurement,  
control, and laboratory use:  
EN 61326 EMC requirements; Minimum Immunity  
EN 55011 Emissions; Group 1, Class A  
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A  
Note For EMC compliance, operate this device  
according to product documentation.  
CE Compliance  
This product meets the essential requirements of applicable  
European Directives, as amended for CE marking, as follows:  
2006/95/EC; Low-Voltage Directive (safety)  
2004/108/EC; Electromagnetic Compatibility Directive  
(EMC)  
NI 9852 Operating Instructions  
22  
ni.com  
 
Note Refer to the Declaration of Conformity (DoC) for  
this product for any additional regulatory compliance  
information. To obtain the DoC for this product, visit  
ni.com/certification, search by model number or  
product line, and click the appropriate link in the  
Certification column.  
Environmental Management  
National Instruments is committed to designing and manufacturing  
products in an environmentally responsible manner. NI recognizes  
that eliminating certain hazardous substances from our products is  
beneficial not only to the environment but also to NI customers.  
For additional environmental information, refer to the NI and the  
Environment Web page at ni.com/environment. This page  
contains the environmental regulations and directives with which  
NI complies, as well as other environmental information not  
included in this document.  
© National Instruments Corp.  
23  
NI 9852 Operating Instructions  
 
Waste Electrical and Electronic Equipment (WEEE)  
EU Customers At the end of their life cycle, all products  
must be sent to a WEEE recycling center. For more  
information about WEEE recycling centers and National  
Instruments WEEE initiatives, visit ni.com/  
environment/weee.htm.  
⬉ᄤֵᙃѻક∵ᶧ᥻
ㅵ⧚
⊩ ˄Ё೑  
˅
RoHS  
Ё೑ᅶ᠋  
݇Ѣ  
ヺড়Ё೑⬉ᄤֵᙃѻકЁ䰤
Փ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ  
DŽ
(RoHS)  
National Instruments  
National Instruments  
Ё೑  
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ ni.com/environment/rohs_chinaDŽ  
RoHS  
ni.com/environment/rohs_china  
(For information about China RoHS compliance, go to  
.)  
NI 9852 Operating Instructions  
24  
ni.com  
 
National Instruments Contact Information  
National Instruments corporate headquarters is located at  
11500 North Mopac Expressway, Austin, Texas, 78759-3504.  
National Instruments also has offices located around the world to  
help address your support needs. For telephone support in the  
United States, create your service request at ni.com/support  
and follow the calling instructions or dial 512 795 8248. For  
telephone support outside the United States, contact your local  
branch office:  
Australia 1800 300 800, Austria 43 662 457990-0,  
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,  
Canada 800 433 3488, China 86 21 5050 9800,  
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,  
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,  
Germany 49 89 7413130, India 91 80 41190000,  
Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196,  
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,  
Malaysia 1800 887710, Mexico 01 800 010 0793,  
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,  
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,  
Portugal 351 210 311 210, Russia 7 495 783 6851,  
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,  
© National Instruments Corp.  
25  
NI 9852 Operating Instructions  
 
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,  
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,  
Taiwan 886 02 2377 2222, Thailand 662 278 6777,  
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545  
NI 9852 Operating Instructions  
26  
ni.com  
 
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the  
Terms of Use section on ni.com/legalfor more information about National Instruments trademarks. Other  
product and company names mentioned herein are trademarks or trade names of their respective companies.  
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,  
the patents.txtfile on your media, or ni.com/patents.  
© 2006–2008 National Instruments Corp. All rights reserved.  
371849B-01  
Jun08  
 

Miele Ventilation Hood DA 8 2 User Manual
Multiquip Automobile Parts MTX60HF User Manual
Multiquip Saw HS81A User Manual
Murphy Switch AS710S User Manual
Nokia Cell Phone 1200 1208 User Manual
Olympus MP3 Player VN PC User Manual
One for All Automobile Parts HFC 302 User Manual
Oregon Scientific Clock RM383PA User Manual
Panasonic Network Card DM0706SY0 User Manual
Panasonic Switch 2SD1450 User Manual