OPERATING INSTRUCTIONS AND SPECIFICATIONS
NI 9481E
4-Channel SPST Electromechanical Relay Module
NI 9481E Dimensions
The following figure shows the dimensions of the NI 9481E.
73.4 (2.89)
0.0 (0.00)
Figure 1. NI 9481E Dimensions in Millimeters (Inches)
© National Instruments Corp.
3
NI 9481E Operating Instructions and Specifications
Connecting the NI 9481E
The NI 9481E has a 10-terminal detachable screw-terminal
connector that provides connections for four electromechanical
relay channels.
3
0
CH0a
CH0b
CH1a
CH1b
CH2a
CH2b
CH3a
CH3b
NC
0
1
2
3
4
5
6
7
8
9
NC
Figure 2. NI 9481E Terminal Assignments
NI 9481E Operating Instructions and Specifications
4
ni.com
Each electromechanical relay channel has two interchangeable
terminals, CHa and CHb.
Each channel has an LED that indicates the state of the channel.
When a channel LED is lit, the channel is on. When the LED is
dark, the channel is off. The LEDs are disabled when the chassis is
in sleep mode. Refer to the Sleep Mode section for more
information about sleep mode.
When connecting a load to the NI 9481E, connect the positive lead
of the load to either the CHa or the CHb terminal, and the ground
of the load to one of the leads of the power supply. Connect the
remaining CHa or CHb terminal to the other lead of the power
supply. Figure 3 shows a possible configuration.
CHa
+
or
–
Load
AC
CHb
NI 9481E
Figure 3. Connecting a Load to the NI 9481E
© National Instruments Corp.
5
NI 9481E Operating Instructions and Specifications
Note You must use 2-wire ferrules to create a secure
connection when connecting more than one wire to a
single terminal on the NI 9481E.
When the channel is turned on, the terminal connected to the load
drives current or applies voltage to the load. When the channel is
off, the terminal does not drive current or apply voltage to the load.
Sleep Mode
This module supports a low-power sleep mode. Support for sleep
mode at the system level depends on the chassis that the module is
plugged into. Refer to the chassis manual for information about
support for sleep mode. If the chassis supports sleep mode, refer to
the software help for information about enabling sleep mode. Visit
ni.com/info and enter cseriesdoc for information about
C Series documentation.
Typically, when a system is in sleep mode, you cannot
communicate with the modules. In sleep mode, the system
consumes minimal power and may dissipate less heat than it does
in normal mode. Refer to the Specifications section for more
information about power consumption and thermal dissipation.
NI 9481E Operating Instructions and Specifications
6
ni.com
Specifications
The following specifications are typical for the range –40 to 85 °C
unless otherwise noted.
Output Characteristics
Number of channels..........................4 electromechanical relay
channels
Relay type.........................................Single pole single throw
(SPST)
Power-on output state .......................Channels off
Switching capacity (resistive load)
Switching voltage.......................60 VDC max, 250 Vrms max
Switching current, per channel
One channel on ....................4 A max at 30 VDC,
1 A max at 60 VDC,
4 A max at 250 Vrms
All channels on ....................2 A max at 30 VDC,
1 A max at 60 VDC,
2 A max at 250 Vrms
© National Instruments Corp.
7
NI 9481E Operating Instructions and Specifications
Resistance per channel,
channel on.........................................50 mΩ
Switching rate...................................1 operation per second
Relay release time.............................5 ms max
Relay operate time............................10 ms max
Relay bounce time ............................3 ms
Off state leakage ...............................10 μA max
Life expectancy
Mechanical (no load)..................20,000,000 operations
Electrical (connecting to load) ...100,000 operations
MTBF ...............................................460,321 hours at 25 °C;
Bellcore Issue 2, Method 1,
Case 3, Limited Part Stress
Method
Note Contact NI for Bellcore MTBF specifications
at other temperatures or for MIL-HDBK-217F
specifications.
NI 9481E Operating Instructions and Specifications
8
ni.com
Power Requirements
Power consumption from chassis
Active mode ...............................580 mW max
Sleep mode .................................5 mW max
Thermal dissipation (at 70 °C)
Active mode ...............................1.5 W max
Sleep mode .................................5 mW max
Physical Characteristics
Use a dry, low-velocity stream of air to clean the module. If
needed, use a soft-bristle brush for cleaning around components.
Screw-terminal wiring ......................12 to 24 AWG copper
conductor wire with 10 mm
(0.39 in.) of insulation
stripped from the end
Torque for screw terminals ...............0.5 to 0.6 N · m
(4.4 to 5.3 lb · in.)
Weight...............................................76 g (2.7 oz)
© National Instruments Corp.
9
NI 9481E Operating Instructions and Specifications
Safety
Safety Voltages
Connect only voltages that are within the following limits.
CHa-to-CHb......................................250 Vrms max,
Measurement Category II
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as
that provided by a standard wall outlet, for example, 115 V for U.S.
or 230 V for Europe.
Caution Do not connect the NI 9481E to signals or use
for measurements within Measurement Categories III
or IV.
Isolation
Channel-to-channel
Continuous...........................250 Vrms
(Basic insulation)
Withstand .............................1,400 Vrms, verified by a 5 s
dielectric withstand test
NI 9481E Operating Instructions and Specifications 10
ni.com
Channel-to-earth ground
Continuous...........................250 Vrms
(Double insulation)
Withstand .............................2,300 Vrms, verified by a 5 s
dielectric withstand test
Safety Standards
This product meets the requirements of the following standards of
safety for electrical equipment for measurement, control, and
laboratory use when installed in a suitable enclosure:
•
•
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1
Note For UL and other safety certifications, refer to the
product label or the Online Product Certification section.
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for
additional regulatory compliance information. To obtain product
certifications and the DoC for this product, visit ni.com/
certification, search by module number or product line, and
click the appropriate link in the Certification column.
© National Instruments Corp.
11 NI 9481E Operating Instructions and Specifications
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more
information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 85 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 85 °C
Operating humidity
(IEC 60068-2-56)..............................10 to 90% RH,
noncondensing
Storage humidity
(IEC 60068-2-56)..............................5 to 95% RH,
noncondensing
Maximum altitude.............................2,000 m
Pollution Degree (IEC 60664)..........2
NI 9481E Operating Instructions and Specifications 12
ni.com
Environmental Management
NI is committed to designing and manufacturing products in an
environmentally responsible manner. NI recognizes that
eliminating certain hazardous substances from our products is
beneficial to the environment and to NI customers.
For additional environmental information, refer to the NI and the
Environment Web page at ni.com/environment. This page
contains the environmental regulations and directives with which
NI complies, as well as other environmental information not
included in this document.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers At the end of the life cycle, all products
must be sent to a WEEE recycling center. For more
information about WEEE recycling centers and National
Instruments WEEE initiatives, visit ni.com/
environment/weee.
© National Instruments Corp.
13 NI 9481E Operating Instructions and Specifications
˅
RoHS
ヺড়Ё⬉ᄤֵᙃ
Ёᅶ᠋
National Instruments
DŽ݇Ѣ
(RoHS)
Ё
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ
RoHS
National Instruments
ni.com/environment/rohs_chinaDŽ
about China RoHS compliance, go to
environment/rohs_china
(For information
ni.com/
.)
Where to Go for Support
The National Instruments Web site is your complete resource for
technical support. At ni.com/support you have access to
everything from troubleshooting and application development
self-help resources to email and phone assistance from
NI Application Engineers.
National Instruments corporate headquarters is located at
11500 North Mopac Expressway, Austin, Texas, 78759-3504.
National Instruments also has offices located around the world to
help address your support needs. For telephone support in the
United States, create your service request at ni.com/support
and follow the calling instructions or dial 512 795 8248. For
NI 9481E Operating Instructions and Specifications 14
ni.com
telephone support outside the United States, contact your local
branch office:
Australia 1800 300 800, Austria 43 662 457990-0,
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 5050 9800,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,
Germany 49 89 7413130, India 91 80 41190000,
Israel 972 3 6393737, Italy 39 02 413091, Japan 81 3 5472 2970,
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,
Malaysia 1800 887710, Mexico 01 800 010 0793,
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,
Portugal 351 210 311 210, Russia 7 495 783 6851,
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,
Taiwan 886 02 2377 2222, Thailand 662 278 6777,
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545
© National Instruments Corp.
15 NI 9481E Operating Instructions and Specifications
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products/technology, refer to the appropriate location: Help»Patents in
your software, the patents.txt file on your media, or the National Instruments Patent Notice at
ni.com/patents.
© 2008 National Instruments Corp. All rights reserved.
372621A-01
Aug08
|