Macurco Carbon Monoxide Alarm SS102H User Manual

MACURCO INC.  
CONTROLLERS & CARBON MONOXIDE DETECTORS  
SS103-3A, SS103-10A  
SS102H, SS102HC-1  
INSTALLATION & OPERATING INSTRUCTIONS  
WWW.MACURCO.COM  
NOTE:  
SUGGESTED WIRE SIZE VS LENGTH OF WIRE BETWEEN EACH SENSOR & CONTROL PANEL  
SIZE  
MAXIMUM DISTANCE  
#18  
#16  
#14  
500 feet  
800 feet  
1250 feet  
GENERAL INFORMATION  
All equipment manufactured by Macurco is thoroughly tested and calibrated before leaving the factory. There is no need to  
re-calibrate the detectors after installation. The equipment is designed to be fully operational after all wiring is completed. For more  
technical and wiring information please refer to the Automatic Exhaust Fan Controllers For Parking Garages & Carbon Monoxide  
Transducers data sheets.  
LOCATION  
Please refer to the attached data sheet titled “Carbon Monoxide System Layouts in Parking Garages”  
SS102H & SS102HC-1 GENERAL INFORMATION  
The SS102H is partially housed in a plastic case, which mounts on and becomes the cover of, a standard 4SD electrical box  
(provided by the installer).  
The SS102HC-1 is housed in a plastic case that is attached to a 4x4 plaster ring. It mounts on any four inch square  
electrical box.  
A low voltage, four conductor, #18 (or larger) cable connects each SS102H, or SS102HC-1 sensor to the SS103 control  
panel. There must be an individual cable between each sensor and its control panel group of four terminals. These terminals are  
labeled on the sensor cover adjacent to the terminal strip. Set up color coding so that the cable will match the same terminals at the  
sensor and control panel. The SS102HC-1 has four pigtail leads: two red for power and a white and black for output. There is an  
internal switch in the SS102HC-1 located on the printed circuit board that must be set to volts.  
SS102H SENSOR OPERATION  
The SS102H sensors have two lights: one green and one red. The green light is a pilot light showing the unit is on and  
operational. When power is first applied to the unit, the green light will be off for 1 1/2 minutes while the sensor goes through a  
warm-up cycle. After this 1 1/2 minute delay, the green light will be on continuously.  
The red light, which is normally off, is part of a supervisory circuit that monitors critical functions of the unit. A failure in  
the sensor is shown by a lighted red light, and at the same time a full range (about 4.8 volts) output on terminal A, to actuate relays  
in the control panel.  
The SS102H was factory calibrated, and cannot be re-calibrated on site. A functional test can be performed by holding a lit  
cigarette (a good source of carbon monoxide) under the SS102H, so smoke drifts up through the sensor. This will cause the SS102H  
to produce an output voltage to actuate the SS103 control panel. If the installation is in a parking garage, a gasoline powered vehicle  
can be operated near the sensor to provide a system test. See the Carbon Monoxide Transducers data sheet for more technical  
information.  
Although the SS102H is usable within a few minutes of being turned on, it will not reach its calibrated level for about 1  
week. The SS102H must be continuously powered.  
1
 
MACURCO CONTROLLERS & DETECTORS (CONT.)  
SS103 OPERATION  
START-UP  
Turn the FAN sensitivity level pots to the center of their ranges. When power is first applied to the SS103, only the Green  
“POWER” light should be on. If SS102HC-1 sensors are used, the appropriate green SENSOR lights on the SS103 will be on, and  
One or more FAN circuits may turn on as the SS102HC-1 goes through its self test cycle, which provides an increasing voltage  
during the warm up cycle. After one and one half minutes, the SS102H sensors will complete their warm-ups, and all SS102  
“SENSOR” green lights should be on. (If not all zones are used on the SS103-3A &-10A only those appropriate green lights will be  
on). These SS103 green lights show the sensors are on and in normal operation, and that the wiring between the sensor and control  
panel is OK. The SS102HC-1 has a 2 1/2 minute warm-up cycle, during which the output voltage progressively increases from 1.0  
to 2.1 volts, which will cause the appropriate SS103 zone lights to actuate.  
Some or all of the Red “SENSOR” lights on the SS103-10A panel may be on at this time. These red lights show when a  
sensor output reaches the level of carbon monoxide to actuate FAN1, FAN2 or FAN3/ALARM. At the same time a SENSOR Red  
light turns on, the amber FAN light or lights start to flash on and off. If the level of CO is high enough, the Red ALARM light also  
will flash on and off. Flashing lights indicate that the time delays before relay turn on has been activated.  
The SS103-3A has multi-colored lights to show sensor status. They will be off on zones to which no sensors are connected.  
Normal operation and clean air is shown by a green sensor light. The light turns amber when “FAN 1” is actuated, then turns red  
when “FAN 2” is exceeded. The ALARM relay is delayed, by the ALARM DELAY setting, from the FAN 2 level setting.  
Allow the system to stabilize for 10 or 20 minutes. All SENSOR red lights, the FAN amber lights, and the red ALARM  
lights should be off once the sensors have warmed up, and the air has been cleared out by the fans.  
SS103-10A  
For the SS103-10A, from the time a “SENSOR” red light turns on, at which time the amber FAN light starts to flash on and  
off, there is a two minute delay before the fan relay is actuated, as shown by a continuous FAN light. Any of the SENSOR red lights  
turn on whenever the Fan sensitivity setting is exceeded at any sensors location. Should the Carbon Monoxide level continue to rise,  
FAN 2 on the SS103-10A will turn on, then the FAN3/ALARM will turn on. At first, the red FAN3/ALARM light flashes on and  
off during the delay period, then turns on steady as the relay closes to actuate the alarm circuit.  
SS103-3A  
The SS103-3A differs in operation in that it has a shorter delay (30 seconds) FAN on and a short (15 second) FAN turn off  
delay. Also, the ALARM range is adjustable continuously from 3 to 33 minutes. This ALARM relay is delayed from the FAN 2  
turn on set point.  
The unit uses 10Amp field replaceable Autofuses on the three output relay circuits to protect them.  
TESTING THE SYSTEM  
The best way to functionally test the systems is to run a car (the older and smog producing the better) near each sensor and  
observe system operation. Make sure the SS103 potentiometers are set in reasonable ranges: The Fans between 50 and 150 and the  
Alarm at 200 or less.  
SS102H  
Functionally test the system by introducing Carbon Monoxide gas into each sensor, while watching for each SS103  
SENSOR red light to turn on. A convenient source of CO is cigarette smoke. Hold a lighted cigarette under each sensor, for several  
minutes, so the smoke drifts up through the sensor. Gas from an unlit butane cigarette lighter can also be used to test the system.  
Shoot the gas into the holes near the lights of the case. If the job specifications require actual CO testing, the SS102HC-1 sensors  
should be used.  
SS102HC-1  
A switch inside the sensor is labeled TEST. Pushing this switch once puts the sensor into a 2 1/2 minute test mode where it  
steps from 1.0 to 2.1 volts. This progressive increase in voltage will cause the SS103 control panel to turn on Fan and Alarm relays  
accordingly. The SS102HC-1 optional Field Calibration Kit (FCK), which includes a cylinder of 50 ppm carbon monoxide gas, can  
be used to test the SS102HC-1 sensors. If the job requires actual CO testing, other cylinders of gas at other levels can be purchased,  
and used with the FCK.  
3
 
MACURCO CONTROLLERS & DETECTORS (CONT.)  
SETTING THE CONTROLS  
If your installation has no pre-determined Fan and Alarm set points, Macurco makes the following suggestions: Set the  
FAN 1 level 50% higher than the average time weighted average of carbon monoxide (CO), usually 50 ppm, that is desired in the  
facility. This will be a FAN 1 setting of 75.  
Set the SS103-10A FAN 2 level 50% higher than FAN 1, or about 112 ppm  
Set the SS103-3A FAN 2 and the SS103-10A ALARM to 200ppm. Set both Alarm Delays to about 30 minutes.  
NOTE: Do not set the SS103-10A ALARM higher than 200 ppm when using SS102HC-1 sensors.  
If the Alarm relay is used to operate a fan, Macurco suggests that the Time Delay be set to about 3 minutes, and on the  
SS103-10A, the ALARM level be set to 50% higher than the FAN 2 or about 170.  
ALARM DELAY PROGRAMMING: SS103-10A  
Set the ALARM adjustment pot to the desired STEL (Short Term Exposure Limit). Usually, this is the Uniform Building  
Code (UBC) standard of 200 ppm. (OSHA suggests using a 200 ppm CEILING, but currently has no standard for STEL for carbon  
monoxide.) To set the Alarm delay on the SS103-10A use the four section programming switch, which is located on the printed  
circuit board near the fan and alarm relays. A chart inside the cover of the case shows the settings for popular delays. Figure 1  
shows more settings.  
Figure 1.  
ON  
OFF  
1
2 3  
50 min.  
4
1
2
3 4  
1
2
3 4  
35 min.  
1 2  
3
4
1
2 3  
8 min.  
4
1
2 3 4  
15 sec.  
44 min.  
25 min.  
NOTE: If using SS102HC-1 sensors, do not set the Alarm above 200.  
ALARM ACTION  
If an alarm is used, a procedure should be set up in the facilities emergency response procedures for what action to take  
when the alarm occurs. Consider the following in making those decisions:  
The Carbon Monoxide levels of 50 ppm averaged over 8 hours and 200 ppm for some time period, are based on full shift  
exposures of workers. This usually does not happen in parking garages, where most people are there for only a few minutes.  
Unless there are full time workers in the facility, Macurco suggests that CO alarms be not considered as life threatening  
emergencies. Instead use them as advisories to check that all control system components are operating OK.  
For the SS102H, in addition to Carbon Monoxide, this system will actuate on smoke and various gases such as gasoline  
fumes, propane, alcohol and other combustible vapors.  
LIMITED WARRANTY  
The SS102H, SS102HC-1, SS103-3A, and SS103-10A gas detectors are warranted to be free from defective material and  
workmanship for a period of one (1) year from the date of installation. If any component becomes defective during the warranty  
period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below. This warranty  
does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise.  
The above warranty is in lieu of all other express warranties, obligations or liabilities. THE IMPLIED WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF ONE (1) YEAR FROM  
THE PURCHASE DATE. Macurco shall not be liable for any incidental or consequential damages for breach of this or any other  
warranty express or implied arising out of or related to the use of said gas detector. Manufacturer or its agent’s liability shall be  
limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of the goods and repayment of the  
price, or repair and replacement of non-conforming goods or parts. (The Uniform Commercial Code applicable in the State of  
Colorado shall govern.)  
RETURN INSTRUCTIONS  
Call (303) 781-4062 for a Return Authorization number. Then carefully pack the gas detector with a written description of  
the nature of the return. Send the unit to the following address:  
Macurco Inc.  
3946 South Mariposa Street  
4
 
Englewood, Colorado 80110  
WWW.MACURCO.COM  
REV. 2/99  
5
 

Lightolier Work Light 24MHT4RF User Manual
Lumex Syatems Personal Lift LF1075 User Manual
Lux Products Thermostat TX500b User Manual
Makita Grinder Angle Grinder User Manual
Marantz Home Theater System SR4600 User Manual
Marley Engineered Products Electric Heater 1800 User Manual
Matsushita Laptop CF 18JHU70TW User Manual
McIntosh Stereo Amplifier MC1201 User Manual
Melissa Vacuum Cleaner 640176 User Manual
Mellerware Food Processor 26888 User Manual